Modbus Protocol
Industrial Modbus TCP/RTU implementation for sensor communication
When to Use
- Reading data from PLCs (Siemens, Allen-Bradley, Schneider)
- Communicating with industrial sensors
- Building SCADA/gateway systems
- Implementing OT (Operational Technology) integrations
Stack
# Rust
tokio-modbus: "0.13+"
# Go
github.com/simonvetter/modbus: latest
# Python
pymodbus: "3.6+"
Modbus Fundamentals
Register Types
| Type | Address Range | Access | Use Case |
|---|---|---|---|
| Coils | 00001-09999 | R/W | Digital outputs (on/off) |
| Discrete Inputs | 10001-19999 | R | Digital inputs (read-only) |
| Input Registers | 30001-39999 | R | Analog inputs (16-bit) |
| Holding Registers | 40001-49999 | R/W | Configuration & data |
Function Codes
| Code | Function | Description |
|---|---|---|
| 01 | Read Coils | Read multiple digital outputs |
| 02 | Read Discrete Inputs | Read digital inputs |
| 03 | Read Holding Registers | Read configuration registers |
| 04 | Read Input Registers | Read analog inputs |
| 05 | Write Single Coil | Set single output |
| 06 | Write Single Register | Write one register |
| 16 | Write Multiple Registers | Write block of registers |
Rust Implementation
Client Setup
use tokio_modbus::prelude::*;
use tokio_modbus::client::tcp;
use std::net::SocketAddr;
use tokio::time::{timeout, Duration};
pub struct ModbusClient {
ctx: client::Context,
timeout_duration: Duration,
}
impl ModbusClient {
pub async fn connect(addr: SocketAddr, slave_id: u8) -> Result<Self, ModbusError> {
let ctx = tcp::connect_slave(addr, Slave(slave_id)).await?;
Ok(Self { ctx, timeout_duration: Duration::from_secs(5) })
}
pub async fn read_holding_registers(&mut self, address: u16, count: u16) -> Result<Vec<u16>> {
timeout(self.timeout_duration, self.ctx.read_holding_registers(address, count))
.await
.map_err(|_| ModbusError::Timeout)?
.map_err(ModbusError::from)
}
pub async fn write_single_register(&mut self, address: u16, value: u16) -> Result<()> {
timeout(self.timeout_duration, self.ctx.write_single_register(address, value))
.await
.map_err(|_| ModbusError::Timeout)?
.map_err(ModbusError::from)
}
}
Data Type Conversions
/// Two 16-bit registers to f32 (big-endian)
pub fn registers_to_f32(regs: &[u16]) -> f32 {
let bytes = [
(regs[0] >> 8) as u8, regs[0] as u8,
(regs[1] >> 8) as u8, regs[1] as u8,
];
f32::from_be_bytes(bytes)
}
/// Two 16-bit registers to f32 (little-endian, swapped)
pub fn registers_to_f32_le(regs: &[u16]) -> f32 {
let bytes = [
regs[1] as u8, (regs[1] >> 8) as u8,
regs[0] as u8, (regs[0] >> 8) as u8,
];
f32::from_le_bytes(bytes)
}
/// f32 to two 16-bit registers
pub fn f32_to_registers(value: f32) -> [u16; 2] {
let bytes = value.to_be_bytes();
[
((bytes[0] as u16) << 8) | (bytes[1] as u16),
((bytes[2] as u16) << 8) | (bytes[3] as u16),
]
}
/// Scale raw value to engineering units
pub fn scale_value(raw: u16, min_raw: u16, max_raw: u16, min_eng: f32, max_eng: f32) -> f32 {
let range_raw = (max_raw - min_raw) as f32;
let range_eng = max_eng - min_eng;
let normalized = (raw - min_raw) as f32 / range_raw;
min_eng + (normalized * range_eng)
}
Sensor Reader
#[derive(Debug, Clone)]
pub struct SensorConfig {
pub id: String,
pub name: String,
pub address: u16,
pub data_type: DataType,
pub unit: String,
pub scale: Option<Scale>,
}
#[derive(Debug, Clone)]
pub enum DataType {
UInt16,
Int16,
Float32,
Float32LE,
}
#[derive(Debug, Clone)]
pub struct SensorReading {
pub sensor_id: String,
pub value: f64,
pub quality: u8, // 192=Good, 128=Uncertain, 0=Bad
pub timestamp: i64,
}
pub struct SensorReader {
client: ModbusClient,
sensors: Vec<SensorConfig>,
}
impl SensorReader {
pub async fn read_sensor(&mut self, sensor: &SensorConfig) -> Result<SensorReading> {
let count = match sensor.data_type {
DataType::UInt16 | DataType::Int16 => 1,
DataType::Float32 | DataType::Float32LE => 2,
};
let registers = self.client.read_holding_registers(sensor.address, count).await?;
let raw_value: f64 = match sensor.data_type {
DataType::UInt16 => registers[0] as f64,
DataType::Int16 => (registers[0] as i16) as f64,
DataType::Float32 => registers_to_f32(®isters) as f64,
DataType::Float32LE => registers_to_f32_le(®isters) as f64,
};
let value = if let Some(scale) = &sensor.scale {
scale_value(raw_value as u16, scale.min_raw, scale.max_raw, scale.min_eng, scale.max_eng) as f64
} else {
raw_value
};
Ok(SensorReading {
sensor_id: sensor.id.clone(),
value,
quality: 192, // Good
timestamp: chrono::Utc::now().timestamp_millis(),
})
}
}
Go Implementation
package modbus
import (
"encoding/binary"
"math"
"sync"
"time"
"github.com/simonvetter/modbus"
)
type Client struct {
client *modbus.ModbusClient
mu sync.Mutex
}
func NewClient(address string, slaveID uint8) (*Client, error) {
client, err := modbus.NewClient(&modbus.ClientConfiguration{
URL: fmt.Sprintf("tcp://%s", address),
Speed: 19200,
Timeout: 5 * time.Second,
})
if err != nil { return nil, err }
if err := client.Open(); err != nil { return nil, err }
client.SetUnitId(slaveID)
return &Client{client: client}, nil
}
func (c *Client) ReadHoldingRegisters(address, count uint16) ([]uint16, error) {
c.mu.Lock()
defer c.mu.Unlock()
return c.client.ReadRegisters(address, count, modbus.HOLDING_REGISTER)
}
func RegistersToFloat32(regs []uint16) float32 {
bytes := make([]byte, 4)
binary.BigEndian.PutUint16(bytes[0:2], regs[0])
binary.BigEndian.PutUint16(bytes[2:4], regs[1])
return math.Float32frombits(binary.BigEndian.Uint32(bytes))
}
Python Implementation
from pymodbus.client import AsyncModbusTcpClient
from dataclasses import dataclass
import struct
@dataclass
class SensorConfig:
id: str
address: int
data_type: str # 'uint16', 'int16', 'float32'
unit: str
class ModbusReader:
def __init__(self, host: str, port: int = 502, slave_id: int = 1):
self.host = host
self.port = port
self.slave_id = slave_id
async def connect(self):
self.client = AsyncModbusTcpClient(self.host, port=self.port)
await self.client.connect()
async def read_holding_registers(self, address: int, count: int):
result = await self.client.read_holding_registers(address, count, slave=self.slave_id)
return result.registers
async def read_sensor(self, config: SensorConfig) -> float:
count = 2 if 'float32' in config.data_type else 1
regs = await self.read_holding_registers(config.address, count)
if config.data_type == 'uint16':
return regs[0]
elif config.data_type == 'int16':
return struct.unpack('>h', struct.pack('>H', regs[0]))[0]
elif config.data_type == 'float32':
bytes_data = struct.pack('>HH', regs[0], regs[1])
return struct.unpack('>f', bytes_data)[0]
PLC Address Maps
Siemens S7-1200/1500
holding_registers:
40001: DB1.DBD0 # Float, first double word in DB1
40003: DB1.DBD4 # Float, second double word
40005: MW100 # Word memory
coils:
00001: Q0.0 # Output bit 0.0
00002: Q0.1 # Output bit 0.1
Allen-Bradley ControlLogix
holding_registers:
40001: N7:0 # Integer file
40002: F8:0 # Float (uses 2 registers)
Schneider Modicon
holding_registers:
40001: %MW0 # Memory word 0
40003: %MF0 # Float (2 registers)
Error Handling
pub fn modbus_error_description(code: u8) -> &'static str {
match code {
0x01 => "Illegal Function",
0x02 => "Illegal Data Address",
0x03 => "Illegal Data Value",
0x04 => "Slave Device Failure",
0x05 => "Acknowledge",
0x06 => "Slave Device Busy",
_ => "Unknown Error",
}
}
Best Practices
Batch Reads
// ✅ Single read for contiguous registers
client.read_holding_registers(40001, 10).await?;
// ❌ Multiple individual reads - slow!
for addr in 40001..40011 {
client.read_holding_registers(addr, 1).await?;
}
Connection Reuse
// ✅ Reuse connection
let client = ModbusClient::connect(addr, slave_id).await?;
for _ in 0..100 {
client.read_holding_registers(addr, count).await?;
}
// ❌ New connection per read
for _ in 0..100 {
let client = ModbusClient::connect(addr, slave_id).await?;
client.read_holding_registers(addr, count).await?;
}
Polling Intervals
| Sensor Type | Recommended Interval |
|---|---|
| Vibration | 10-50ms |
| Temperature/Pressure | 500ms-1s |
| Level/Flow totals | 5-10s |
Quick Reference
| Task | Rust |
|---|---|
| Read holding | ctx.read_holding_registers(addr, count).await |
| Read input | ctx.read_input_registers(addr, count).await |
| Write single | ctx.write_single_register(addr, value).await |
| Write multiple | ctx.write_multiple_registers(addr, &values).await |
| Read coils | ctx.read_coils(addr, count).await |
Quality Codes (OPC UA)
| Code | Meaning |
|---|---|
| 192 (0xC0) | Good |
| 128 (0x80) | Uncertain |
| 0 (0x00) | Bad |
Resources